NAYCY-O 0.6/1kV - Power cables with aluminium conductors and with copper concentric conductor

Application: In dry, humid and wet locations, cable ducts, outdoors, underground and in water

Construction:
                    1.Conductor Aluminium sector-shape conductor class 2 acc. to IEC 60228
                    2.Insulation Polyvinylchloride (PVC) type DIV 4
                    3.Filling PVC inner sheath
                    4.Screening Concentric conductor of cooper wires and copper tape
                    5.Outer sheath Polyvinylchloride (PVC), Black type DMV 5

Standards: DIN VDE 0276-603
                 IEC 60502
                 CPR - classification according to EN 50575

Core identification: HD 308 S2

License: This cable is VDE certified

Tridimensional view

Cable Specifications

   Electrical Performance:
      Nominal Voltage: 600 / 1000 Volt
      Test voltage [V]AC 4000
      Short circuit time max. sec 5
      Bending radius in motion x diameter 15

   Temperature range: in motion 70°C
      Operating temperature: short circuit 160°C

   Fire classification CPR class:
      Reaction to fire EN 60332-1-2
      CPR - Eca