Application: This power cable is suitable for fixed installations, preferably in cable ducts, indoors, outdoors, in water or underground if no mechanical damage is to be expected.
Construction:
1.Conductor - solid (SE) or stranded (RM/SM) aluminium wires
2.Insulation - core insulation of polyvinylchloride (PVC)
3.Filling - PVC core covering or taping
4.Outher sheath - outer sheath of polyvinylchloride(PVC), black
Standards: HD 603 S1/3G
DIN EN 60228 class 1 and 2 – Construction
HD 308 S2 (core identification)
Construction according to EN 60228
License: This cable is VDE certified
Electrical Performance:
Nominal Voltage: 600 / 1000 Volt
Test Voltage: [V]AC 4000
Short circuit time max. [sec] 5
Bending radius: Single core x diameter 15
Multi core x diameter 12
Temperature range: in motion: -5°C till +70°C
Fixed: -20°C till +70°C
Operating temperature short circuit 160°C <=300mm2
140°C > 300mm2
Flammability: Reaction to fire 50575 - Eca